Thickness for Pipes and Fittings (DN 80 to DN 2000) - Supplier : Environmech Sdn Bhd (Selangor Area)

Thickness for Pipes and Fittings (DN 80 to DN 2000) - Supplier : Environmech Sdn Bhd (Selangor Area)



The thickness of pipes and fittings has been calculated as a function of the nominal size DN by using the formula:
e = K (0.5 + 0.001DN) with the following values for K.
K = 9 for pipes, thus
e=4.5 + 0.009DN
K=14 for tees, thus
e=7 + 0.014DN
K=12 for other fittings, thus
e=6 + 0.012DN
The thickness of the pipes has been limited to 6mm and fitting to 7mm.