ABS Nopon disc diffuser system PIK 300
Diffuser data
Design air flow range | 1,5 -8,0 m³/h/diffuser (x (+20°C ; 1013 mbar) |
Diffuser level | 250mm (xx |
Air temperature, max | + 100°C |
Max/min assembly depth | 3 – 8 m (optimal) (xxx |
Diffuser diameter | 336 mm |
Disc surface area | 0,060 m2 |
Size of bubbles | 1 – 3 mm |
Diffuser weight | 0,795 kg |
Max/min interval, c/c | 1,25 / 0,4 m |
x) When waste water contains chemicals harmful to EPDM or when water temperature is
>30°C or air temperature is close to 80°C, a lower maximum air flow should be used.
A peak value of 10 m3/h can be used for max. of 15 min only e.g. for cleaning the membrane.
Using air flow less than 1,5 m3/h must be consulted with ABS.
xx) Recommended measure from basin bottom to diffuser top
xxx) Consult ABS on depths outside the range
For more information or enquiry, please contact Environmech Sdn. Bhd.
Contact us: http://www.environmech.com/p/contact-us.html
Contact us: http://www.environmech.com/p/contact-us.html
Website: www.Environmech.com